BRAND | Thermokon |
Product | 769266 |
Description | room operating device |
Internal code | IMP4532688 |
Weight | 0.06 |
Custom code | 90271010 |
Technical specification | NOVOS 3 PTD white CO2+VOC Temp_RH RS485 Modbus Room operating device 4 measured variables — Modbus Network technology: RS485 Modbus Temperature measuring range: 0.. +50 °C, accuracy: ±0.5 K (typically at 21 °C) Humidity measuring range: 0..100% rH (enthalpy, abs. humidity & dew point can be optionally parameterized via Thermokon NovoSapp or BUS), rel. humidity accuracy: ± 2% between 10..90% rH (typically at 21 °C) CO2 measuring range: 0.. 2000 ppm | 0.. 5000 ppm (optionally parameterizable via Thermokon NovosApp), Accuracy: ±50 ppm (dual channel self-calibration) VOC measurement range: 0.. 100% (self-calibration) Input: 1x input for floating contact Power supply: 15.. 35 V = or 19.. 29 V ~ Housing: NOVOS 3, PC V0, pure white, IP20, 110x100.5x23 mm (LxWxH) Electrical connection: Tool-free spring-loaded terminal Controls (standard lettering): - potentiometers (-,<Skala>, +) - Presence detection button with LED 24 V = (LED is also used for TLF function/indication of air quality) |
Please send us your request per e-mail, so we can send you our offer with competitive prices and delivery time for Thermokon - 769266 room operating device number or any other model you need. We can offer competitive price, and delivery time with wide products distribution network in United Kingdom Industrial products Market.