BRAND | Siemens (Landis Gyr) |
Product | RLU202 |
Description | Universal Controller |
Internal code | IMP3764215 |
Weight | 0.44 |
Custom code | 85371091 |
Technical specification | rated voltage Ext. Requirements Safety transformer after AC 24V r20% (SELV) EN 60 742/EN 61 558-2-6, minimum 10 VA, maximum 320 VA Frequency 50/60 Hz power consumption RLU202, RLU220, RLU222 RLU232, RLU236 5 VA 6 VA Supply line protection Melting protection max. 10 A sluggish or Line protection switch max. 13 A Release characteristic B, C, D according to EN 60898 or Power supply with current limit of max. 10 A For numbers, see “Type overview” feeler passively actively LG-Ni 1000, T1, Pt1000 2x LG-Ni 1000 (averaging) DC 0... 10 V givers passively actively 0... 1000:/1000... 1175: DC 0... 10 V Contact query voltage stream DC 15 V 5mA Requirements for signaling and impulse contacts signal coupling type of contact Insulation resistance to network potential potential-free Continuous or impulse contacts AC 3750 V in accordance with EN 60 730 Permitted resistor when contacts are closed for open contacts up to 200: min. 50 k: |
Please send us your request per e-mail, so we can send you our offer with competitive prices and delivery time for Siemens (Landis Gyr) - RLU202 Universal Controller number or any other model you need. We can offer competitive price, and delivery time with wide products distribution network in United Kingdom Industrial products Market.
WE SELL ONLY NEW AND ORIGINAL PRODUCTS!